Appendix d remote mounting, Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual
Page 271
Reference Manual
00809-0100-4530, Rev BA
July 2009
D-1
Rosemount 5300 Series
Appendix D
Remote Mounting
Remote Housing, New Units . . . . . . . . . . . . . . . . . . . . . . . page D-1
Remote Connection, Field Retrofit . . . . . . . . . . . . . . . . . . page D-3
Remote Housing Configuration . . . . . . . . . . . . . . . . . . . . . page D-4
REMOTE HOUSING,
NEW UNITS
Remote Housing can be used to place the head apart from the probe if it is in
a hot or vibrating place. With Remote Housing, you can place the transmitter
head in a better position to be able to read the display, for example.
The remote housing assembly is shipped with the transmitter head mounted
on the probe and the remote connection in a separate box.
The transmitter head must have the remote connection installed before
functioning.
The parts in the shipping unit consist of:
•
Transmitter head mounted on probe
•
Remote connection
•
Bracket kit
- Bracket (1 pcs)
- Clamping bracket (4 pcs)
- U-bolt (2 pcs)
- M6 screw (3 pcs)
- M6 nut (4 pcs)
M50 nut
Remove the transmitter head from the
probe
Remove the transmitter head from the probe
by unscrewing the M50 nut.
Mount the probe in the tank