beautypg.com

Appendix i resource transducer block, Appendix i: resource transducer block an, Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 299: Reference manual, Overview, Parameters and descriptions

background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

I-1

Rosemount 5300 Series

Appendix I

Resource Transducer Block

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page I-1
Parameters and Descriptions . . . . . . . . . . . . . . . . . . . . . . page I-1

OVERVIEW

This section contains information on the Rosemount 5300 Series Radar Level
Transmitter Resource Block. Descriptions of all Resource Block Parameters,
errors, and diagnostics are included. Also the modes, alarm detection, status
handling, and troubleshooting are discussed.

Definition

The resource block defines the physical resources of the device. The
resource block also handles functionality that is common across multiple
blocks. The block has no linkable inputs or outputs.

PARAMETERS AND
DESCRIPTIONS

The table below lists all the configurable parameters of the Resource Block,
including the descriptions and index numbers for each.

Parameter

Index

Number

Description

ACK_OPTION

38

Selection of whether alarms associated with the function block will be
automatically acknowledged.

ADVISE_ACTIVE

82

Enumerated list of advisory conditions within a device.

ADVISE_ALM

83

Alarm indicating advisory alarms. These conditions do not have a direct impact on the
process or device integrity.

ADVISE_ENABLE

80

Enabled ADVISE_ALM alarm conditions. Corresponds bit for bit to the ADVISE_ACTIVE.
A bit on means that the corresponding alarm condition is enabled and will be detected. A
bit off means the corresponding alarm condition is disabled and will not be detected.

ADVISE_MASK

81

Mask of ADVISE_ALM. Corresponds bit of bit to ADVISE_ACTIVE. A bit on means that
the condition is masked out from alarming.

ADVISE_PRI

79

Designates the alarming priority of the ADVISE_ALM

ALARM_SUM

37

The current alert status, unacknowledged states, unreported states, and disabled states
of the alarms associated with the function block.

ALERT_KEY

04

The identification number of the plant unit.

BLOCK_ALM

36

The block alarm is used for all configuration, hardware, connection failure or system
problems in the block. The cause of the alert is entered in the subcode field. The first alert
to become active will set the Active status in the Status parameter. As soon as the
Unreported status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active status, if the subcode has changed.

BLOCK_ERR

06

This parameter reflects the error status associated with the hardware or software
components associated with a block. It is a bit string, so that multiple errors may be
shown.

CLR_FSTATE

30

Writing a Clear to this parameter will clear the device FAIL_SAFE if the field condition has
cleared.

CONFIRM_TIME

33

The time the resource will wait for confirmation of receipt of a report before trying again.
Retry will not happen when CONFIRM_TIME=0.

CYCLE_SEL

20

Used to select the block execution method for this resource. The Rosemount 5300
supports the following:
Scheduled: Blocks are only executed based on the function block schedule.
Block Execution: A block may be executed by linking to another blocks completion.