Application example 3 -44, Rosemount 5300 series, Reference manual – Emerson Process Management ROSEMOUNT 5300 User Manual
Page 116: Application example 3
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
5-44
Application Example 3
Radar Level Transmitter, Product Level and Interface Level Value
A level transmitter is measuring the product level and the interface level in a
33 ft. (10 m) high tank. The maximum interface level is 10 ft. (3 m).
Figure 5-16. Situation Diagram
Solution
Table 5-11 lists the appropriate configuration settings, and Figure 5-17
illustrates the correct function block configuration.
Table 5-11. Analog Input
Function Block Configuration for
a Level and Interface
Transmitter
Figure 5-17. Analog Input
Function Block Diagram for a
Level and Interface Transmitter
10 ft
(3 m)
100%
0%
33 ft
(10 m)
100%
0%
AI Function Block Product Level
AI Function Block Interface Level
Parameter
Configured Values
Parameter
Configured Values
L_TYPE
Direct
L_TYPE
Direct
XD_SCALE
Not Used
XD_SCALE
Not Used
OUT_SCALE
Not Used
OUT_SCALE
Not Used
CHANNEL
CH1: Level
CHANNEL
CH11: Interface Level
Level Measurement
To Another
Function Block
OUT_D
OUT
AI Function Block
AI Function Block
(Product Level)
To Another
Function Block
To Another
Function Block
OUT_D
OUT
AI Function Block
AI Function Block
(Interface Level)
To Another
Function Block
Interface Level Measurement