Foundation fieldbus error messages -44, Resource block -44, Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual
Page 174: Reference manual, Foundation fieldbus error messages resource block
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
7-44
FOUNDATION FIELDBUS
ERROR MESSAGES
Resource Block
This section describes error conditions found in the Resource block. Read
Table 7-13 through Table 7-15 to determine the appropriate corrective action.
Block Errors
Table 7-13 lists conditions reported in the BLOCK_ERR parameter.
Table 7-13. Resource Block
BLOCK_ERR messages
Table 7-14. Resource Block
SUMMARY_STATUS messages
Table 7-15. Resource Block
DETAILED_STATUS with
recommended action messages
Condition Name and Description
Other
Simulate Active: This indicates that the simulation switch is in place.
This is not an indication that the I/O blocks are using simulated data
Device Fault State Set
Device Needs Maintenance Soon
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory
Lost Static Data: Static data that is stored in non-volatile memory has been lost
Lost NV Data: Non-volatile data that is stored in non-volatile memory has been lost
Device Needs Maintenance Now
Out of Service: The actual mode is out of service
Condition Name
Uninitialized
No repair needed
Repairable
Call Service Center
Condition Name
Recommended Action
LOI Transducer block error
1. Restart processor
2. Check display connection
3. Call service center
Sensor Transducer block error
1. Restart processor
2. Check Rosemount 5300 cable
3. Call service center
Mfg. Block integrity error
1. Restart processor
2. Call service center
Non-Volatile memory integrity error
1. Restart processor
2.Call service center
ROM integrity error
1. Restart processor
2. Call service center