Rosemount 5300 series, Reference manual – Emerson Process Management ROSEMOUNT 5300 User Manual
Page 296
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
H-2
AMPLITUDE_THRESHOLD_CURVE
13
ATC: filters out weak disturbance echoes and noise.
SIMULATION_MODE
14
Simulation of measurement values.
SET_CONSTANT_THRESHOLD
15
A constant amplitude threshold can be used to filter out noise.
RADAR_LEVEL_RANGE
16
RADAR_LEVEL_SIGNAL_STRENGT
H_RANGE
17
RADAR_VOLUME_RANGE
18
ENV_PRESENTATION
19
PROBE_END_THRESH
20
This threshold is used to locate the probe end echo. The probe
end echo is used by the device to know when the tank is empty,
but is sometimes also useful when no surface echo can be found.
REFERENCE_THRESH
21
This threshold is used to locate the reference echo.
INTERFACE_THRESH
22
This threshold is used to block out disturbing echoes and noise
when locating the interface echo.
FULL_TANK_THRESH_OFFSET
23
By adding an offset to the Reference Threshold it is possible for
the device to determine when the tank is full. If the reference echo
amplitude is between the Reference Threshold and the Full Tank
Threshold then the tank is considered full.
PEP_PRODUCT_DC
24
Enter the product dielectric constant for the product in the tank.
AUTO_CONF_MEAS_FUNC
25
ECHO_TIME_OUT
26
Change this parameter to define the time in seconds before the
device should start to search for a surface echo after it has been
lost.
CLOSE_DIST
27
This parameter defines a window centered at the current surface
position where new surface echo candidates can be selected. The
size of the window is +/-Close Distance. Echoes outside this
window will not be considered as surface echoes.
USED_PROBE_END_THRESH
28
Probe End Threshold currently used in the device.
USED_REFERENCE_THRESH
29
Reference Threshold currently used in the device.
USED_INTERFACE_THRESH
30
Interface Threshold currently used in the device.
USED_TANK_PRESENTATION
31
USED_ECHO_TIME_OUT
32
Echo Timeout currently used in the device.
USED_CLOSE_DIST
33
Close Distance currently used in the device.
SW_SUPPORT2
34
Defines what options are enabled in the device.
USED_HOLD_OFF_DIST
35
The upper null zone distance currently used in the device.
USED_PEP_PRODUCT_DC
36
Product Dielectric currently used in the device.
START_CODE
37
This code determines what options are available in your device.
Do not change your Start Code unless you have received a valid
one. Use Enter Start Codes method to change it.
UNIT_CODE
38
Unit code 1 -4 can be sent to your local Emerson representative in
order to receive new Start Codes for upgrading your device.
ENV_SET_START_CODE
39
Set Start Code
PROBE_END_ANCHORING
40
PEP_PROBE_END_OFFSET
41
USED_PEP_ PROBE_END_OFFSET
42
VOL_VOLUME_CALC_METHOD
43
Choose what kind of volume calculation method to use.
VOL_IDEAL_DIAMETER
44
Diameter of the tank (only for ideal tank shapes).
VOL_IDEAL_LENGTH
45
Length/height of the tank (only for ideal tank shapes).
Parameter
Index
Number
Description