Reference Manual

00809-0100-4530, Rev BA
July 2009

D-3

Rosemount 5300 Series

REMOTE CONNECTION,
FIELD RETROFIT

To upgrade a currently installed Rosemount 5300 transmitter with a remote
housing, the embedded software needs revision 2.A2 or later, and the Spare
Part Kit (03300-3001-000X) must be ordered.

The Rosemount 5300 transmitter head must be configured for remote
housing to work.

The Spare Part Kit consists of:

Remote connection

Bracket kit

- Bracket (1 pcs)

- Clamping bracket (4 pcs)

- U-bolt (2 pcs)

- M6 screw (3 pcs)

- M6 nut (4 pcs)

Mount the bracket to the pole

Mount the bracket to the pole, making sure the distance between the probe
and bracket does not exceed the length of the remote connection.

1. Put the two U-bolts through the holes of the bracket. Several holes are

available for vertical/horizontal pipe mounting.

2. Put the clamping brackets on the U-bolts and around the pipe.

Use the supplied nuts to fasten the bracket to the pipe.

Fasten the housing support to the bracket

Fasten the housing support to the bracket using the M6 screws. The screws
are threaded through the top of the mounting bracket and into the housing
support.

Remove the transmitter head from the probe

Remove the transmitter head from the probe by unscrewing the M50 nut.

Mount the probe housing on the probe

Mount the probe housing on the probe, making sure that the M50 nut is

properly tightened.

Connect the transmitter head on the housing support

Connect the transmitter head on the housing support, making sure that the

M50 nut is properly tightened.