Rosemount 5300 series, Reference manual, Block errors – Emerson Process Management ROSEMOUNT 5300 User Manual
Page 312: Modes
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
J-6
BLOCK ERRORS
Table J-2 lists conditions reported in the BLOCK_ERR parameter.
Table J-2. BLOCK_ERR
Conditions
MODES
The AI Function Block supports three modes of operation as defined by the
MODE_BLK parameter:
•
Manual (Man) The block output (OUT) may be set manually
•
Automatic (Auto) OUT reflects the analog input measurement or the
simulated value when simulation is enabled
•
Out of Service (O/S) The block is not processed. FIELD_VAL and PV
are not updated and the OUT status is set to Bad: Out of Service. The
BLOCK_ERR parameter shows Out of Service. In this mode, you can
make changes to all configurable parameters. The target mode of a
block may be restricted to one or more of the supported modes.
Condition
Number
Condition Name and Description
0
Other
1
Block Configuration Error: the selected channel carries a measurement that
is incompatible with the engineering units selected in XD_SCALE, the
L_TYPE parameter is not configured, or CHANNEL = zero.
2
Link Configuration Error
3
Simulate Active: Simulation is enabled and the block is using a simulated
value in its execution.
4
Local Override
5
Device Fault State Set
6
Device Needs Maintenance Soon
7
Input Failure/Process Variable has Bad Status: The hardware is bad, or a
bad status is being simulated.
8
Output Failure: The output is bad based primarily upon a bad input.
9
Memory Failure
10
Lost Static Data
11
Lost NV Data
12
Readback Check Failed
13
Device Needs Maintenance Now
14
Power Up
15
Out of Service: The actual mode is out of service.