beautypg.com

Rosemount 5300 series, Reference manual, Block errors – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 312: Modes

background image

Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

J-6

BLOCK ERRORS

Table J-2 lists conditions reported in the BLOCK_ERR parameter.

Table J-2. BLOCK_ERR
Conditions

MODES

The AI Function Block supports three modes of operation as defined by the
MODE_BLK parameter:

Manual (Man) The block output (OUT) may be set manually

Automatic (Auto) OUT reflects the analog input measurement or the
simulated value when simulation is enabled

Out of Service (O/S) The block is not processed. FIELD_VAL and PV
are not updated and the OUT status is set to Bad: Out of Service. The
BLOCK_ERR parameter shows Out of Service. In this mode, you can
make changes to all configurable parameters. The target mode of a
block may be restricted to one or more of the supported modes.

Condition

Number

Condition Name and Description

0

Other

1

Block Configuration Error: the selected channel carries a measurement that
is incompatible with the engineering units selected in XD_SCALE, the
L_TYPE parameter is not configured, or CHANNEL = zero.

2

Link Configuration Error

3

Simulate Active: Simulation is enabled and the block is using a simulated
value in its execution.

4

Local Override

5

Device Fault State Set

6

Device Needs Maintenance Soon

7

Input Failure/Process Variable has Bad Status: The hardware is bad, or a
bad status is being simulated.

8

Output Failure: The output is bad based primarily upon a bad input.

9

Memory Failure

10

Lost Static Data

11

Lost NV Data

12

Readback Check Failed

13

Device Needs Maintenance Now

14

Power Up

15

Out of Service: The actual mode is out of service.