beautypg.com

Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 57

background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

3-27

Rosemount 5300 Series

Rigid Single Lead probe (8 mm)

NOTE!
The washer should not be used if the disc material is C-276.

NOTE!
Centering discs may not be used with PTFE covered probes.

To avoid bending the probe (rigid probes), or twisting and coming into contact
with the chamber wall (flexible probes), a small clearance distance between
centering disk and chamber bottom is recommended. The clearance distance
of 1 in. (25 mm) is selected with a dome shaped chamber bottom in mind,
which may prevent the centering disk from reaching the bottom.

1. Mount the centering disc at the

end of the probe.

2. Fasten the disc by inserting the

split pin through the bushing
and the probe.

3. Secure the split pin.

Bushing

Split pin

A clearance distance
of 1 in. (25 mm)
between the probe
end and the chamber
bottom is
recommended.

Bushing