Rosemount 5300 series, Reference manual, Configure the ai block – Emerson Process Management ROSEMOUNT 5300 User Manual
Page 315
Reference Manual
00809-0100-4530, Rev BA
July 2009
J-9
Rosemount 5300 Series
CONFIGURE THE AI
BLOCK
A minimum of four parameters are required to configure the AI Block. The
parameters are described below with example configurations shown at the
end of this section.
CHANNEL
Select the channel that corresponds to the desired sensor measurement. The
Rosemount 5300 measures Level (channel 1), Distance (channel 2), Level
Rate (channel 3), Signal Strength (channel 4), Volume (channel 5), Internal
Temperature (channel 6), Upper Product Volume (channel 7), Lower Product
Volume (channel 8), Interface Distance (channel 9), Upper Product Thickness
(channel 10), Interface Level (channel 11), Interface Level Rate (channel 12),
and Interface Signal Strength (channel 13).
L_TYPE
The L_TYPE parameter defines the relationship of the transmitter
measurement (Level, Distance, Level Rate, Signal Strength, Volume, and
Average Temperature) to the desired output of the AI Block. The
relationship can be direct or indirect root.
Direct
Select direct when the desired output will be the same as the transmitter
measurement (Level, Distance, Level Rate, Signal Strength, Volume, and
Average Temperature).
Indirect
Select indirect when the desired output is a calculated measurement
based on the transmitter measurement (Level, Distance, Level Rate,
Signal Strength, Volume, and Average Temperature). The relationship
between the transmitter measurement and the calculated measurement
will be linear.
AI Block
TB Channel Value Process Variable
Level
1
CHANNEL_RADAR_LEVEL
Ullage
2
CHANNEL_RADAR_ULLAGE
Level Rate
3
CHANNEL_RADAR_LEVELRATE
Signal Strength
4
CHANNEL_RADAR_SIGNAL_STRENGTH
Volume
5
CHANNEL_RADAR_VOLUME
Internal Temperature
6
CHANNEL_RADAR_INTERNAL_TEMPERATURE
Upper Product
Volume
7
CHANNEL_UPPER_PRODUCT_VOLUME
Lower Product
Volume
8
CHANNEL_LOWER_ PRODUCT_VOLUME
Interface Distance
9
CHANNEL_INTERFACE_ DISTANCE
Upper Product
Thickness
10
CHANNEL_UPPER_ PRODUCT_THICKNESS
Interface Level
11
CHANNEL_INTERFACE_LEVEL
Interface Level Rate
12
CHANNEL_INTERFACE_ LEVELRATE
Interface Signal
Strength
13
CHANNEL_INTERFACE_ SIGNALSTRENGTH
Signal Quality
14
CHANNEL_SIGNAL_QUALITY
Surface/Noise Margin
15
CHANNEL_ SURFACE_NOISE_MARGIN
Vapor DC
16
CHANNEL_VAPOR_DC