Rosemount 5300 series, Reference manual, Remote housing measuring range – Emerson Process Management ROSEMOUNT 5300 User Manual
Page 192
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
A-8
Remote Housing
Measuring Range
This table shows the maximum recommended measuring range with Remote
Housing for different RH lengths, installation types, Dielectric Constants, and
probe types.
Table A-2. Remote Housing
measuring range
Dielectric
Constant
Rigid Single
8 mm
Rigid Single
13 mm
Flexible Single
Coaxial
Rigid Twin
Flexible Twin
1 m
Remote
Housing
Chamber / pipe
installations
≤ 4 in.
(100 mm)
1.4
2
80
1.4
2
80
4 ft (1.25 m)
10 ft (3 m)
(1)
10 ft (3 m)
4 ft (1.25 m)
4 ft (1.25 m)
10 ft (3 m)
(1)
15 ft (4.5 m)
(1)
15 ft (4.5 m)
(1)
15 ft (4.5 m)
(1)
4 ft (1.25 m)
4 ft (1.25 m)
10 ft (3 m)
(1)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
4 ft (1.25 m)
4 ft (1.25 m)
159 ft (48.5 m)
(1)
19 ft
(6 m)
10 ft (3 m)
(1)
10 ft (3 m)
(1)
10 ft (3 m)
(1)
4 ft (1.25 m)
4 ft (1.25 m)
10 ft (3 m)
(1)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
4 ft (1.25 m)
98 ft (30 m)
(1)
159 ft (48.5 m)
(1)
Tank installations
2 m
Remote
Housing
Chamber / pipe
installations
≤ 4 in.
(100 mm)
1.4
2
80
1.4
2
80
9 ft (2.75 m)
10 ft (3 m)
(1)
10 ft (3 m)
9 ft (2.75 m)
9 ft (2.75 m)
10 ft (3 m)
(1)
15 ft (4.5 m)
(1)
15 ft (4.5 m)
(1)
15 ft (4.5 m)
9 ft (2.75 m)
9 ft (2.75 m)
10 ft (3 m)
(1)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
9 ft (2.75 m)
9 ft (2.75 m)
154 ft (47 m)
(1)
19 ft
(6 m)
10 ft (3 m)
(1)
10 ft (3 m)
(1)
10 ft (3 m)
(1)
9 ft (2.75 m)
9 ft (2.75 m)
10 ft (3 m)
(1)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
9 ft (2.75 m)
98 ft (30 m)
(1)
154 ft (47 m)
(1)
Tank installations
3 m
Remote
Housing
Chamber / pipe
installations
≤ 4 in.
(100 mm)
1.4
2
80
1.4
2
80
10 ft (3 m)
15 ft (4.5 m)
15 ft (4.5 m)
15 ft (4.5 m)
14 ft (4.25 m)
14 ft (4.25 m)
15 ft (4.5 m)
(1)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
14 ft (4.25 m)
14 ft (4.25 m)
149 ft (45.5 m)
(1)
19 ft
(6 m)
10 ft (3 m)
(1)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
33 ft (10 m)
(1)
(2)
14 ft (4.25 m)
98 ft (30 m)
(1)
149 ft (45.5 m)
(1)
Tank installations
(1) Accuracy may be affected up to + 1.2 in. (30 mm).
(2) Required chamber/pipe size is 3 or 4 in. (75 -100 mm).