FACTORY MUTUAL (FM)
APPROVALS
The Rosemount 5300 Series Guided Wave Radar Level Transmitter that have
the following labels attached have been certified to comply with the
requirements of the approval agencies noted.
Intrinsic Safety
Figure B-9. Approval Labels
Factory Mutual (FM) HART
model
I5
Intrinsically Safe for Class I, II, III, Division 1, Groups A, B, C, D, E, F
and G.
Class I, Zone 0, AEX ia IIC T4 when installed per Control Drawing:
9240030-936.
Non-incendive for Class I, Division 2, Groups A, B, C and D.
Suitable for Class II, III, Division 2, Groups F and G.
4-20 mA/HART model: U
i
=30 V, I
i
=130 mA, P
i
=1.0 W, C
i
=7.26 nF, L
i
=0.
Max operation 42.4 V, 25 mA.
Temperature code T4.
Ambient Temperature Limits: -50
°
C to + 70 °C.