Application Example 2

Radar Level Gauge, Level value in percent (%)

The maximum level in the tank is 46 ft. (14 m). The level value is displayed in
percentage of the full span (see Figure 5-14).

Figure 5-14. Situation Diagram

Solution

Table 5-10 lists the appropriate configuration settings, and Figure 5-15
illustrates the correct function block configuration.

Table 5-10. Analog Input
Function Block Configuration for
a Level Transmitter where level
output is scaled between
0-100%

Figure 5-15. Function Block
Diagram for a Level Transmitter
where level output is scaled
between 0-100%

46 ft.
(14 m)

100%

0%

Parameter

Configured Values

L_TYPE

Indirect

XD_SCALE

0 to 14 m

OUT_SCALE

0 to 100%

CHANNEL

CH1: Level

Level Measurement - percent

AI Function Block

OUT_D

OUT

0 to 100%