This section describes error conditions found in the Sensor Transducer Block.
Table 7-16. Transducer Block
BLOCK_ERR messages
Table 7-17. Transducer Block
XD_ERR messages
Analog Input (AI)
Function Block
This section describes error conditions that are supported by the AI Block.
Read Table 7-19 to determine the appropriate corrective action.
Table 7-18. AI BLOCK_ERR
Conditions
.
Condition Name and Description
Other
Out of Service: The actual mode is out of service
Condition Name and Description
Electronics Failure: An electrical component failed
I/O Failure: An I/O failure occurred
Data Integrity Error: Data stored in the device is no longer valid due to a non-volatile memory
checksum failure, a data verify after write failure, etc.
Algorithm Error: The algorithm used in the transducer block produced an error due to
overflow, data reasonableness failure, etc.
Condition
Number
Condition Name and Description
0
Other
1
Block Configuration Error: the selected channel carries a measurement that
is incompatible with the engineering units selected in XD_SCALE, the L_TYPE
parameter is not configured, or CHANNEL = zero
3
Simulate Active: Simulation is enabled and the block is using a simulated
value in its execution
7
Input Failure/Process Variable has Bad Status: The hardware is bad, or a
bad status is being simulated
14
Power Up
15
Out of Service: The actual mode is out of service