22

Introduction

14. Enter values for both the VirtFB/count1 and VirtFB/count2 points. Observe the following:

• The Math Function/in1 and Math Function/in2 data points in the FPM are updated to the

same values as the dynamic data points on the SmartServer to which they are connected. The
Web connections keep these sets of data points synchronized.

• The Math Function/out1 FPM output data point is updated to reflect the sum of the in1 and

in2 FPM input points.

• The VirtFB/total count data point on the SmartServer is updated to match the new sum

stored in the Math Function/out1 FPM data point.

For more information on using L

ON

W

ORKS

connections and Web connections to connect the data

points declared in an FPM device, see Chapter 6, Deploying FPMs on a SmartServer. For more
information on using the Web Binding application, including how to validate, delete, and add
attachments to bindings, see Chapter 4 of the i.LON SmartServer 2.0 User’s Guide.