Writing an fpm driver, Writing the fpm driver initialize() routine – Echelon i.LON SmartServer 2.0 User Manual

Page 100

background image

86

Creating Freely Programmable Modules

void CUFPTHVACController::Shutdown()

{
m_oTimer1.Stop();
StopAllTimers();
}

See the Programmer’s Reference in Appendix A for more information on stopping timers.

Writing an FPM Driver

You can write an FPM driver using the i.LON SmartServer 2.0 Programming Tool. An FPM driver
creates data points on the SmartServer and provides values for them by reading and writing to the RS-
232 and RS-485 ports on the SmartServer. To create an FPM driver, you specify the logic to be
executed on the data points in the following four routines: Initialize(),Work(), Shutdown(),
OnTimer()

:

• The Initialize() routine is executed when the FPM driver is started or enabled. In the

Initialize()

routine, you start timers using the Start() method of the CFPM_Timer class

or the START_TIMER() macro, open the RS-232 and RS-485 ports on the SmartServer, and
write to the properties of the data points declared in the FPM driver.

• The Work() routine is executed when one or more data points declared in the FPM driver are

updated. In the Work() routine, you write one or more IF-THEN(-ELSE) statements that
evaluate whether the values of the data points in the FPM have been updated. If the data points
have been updated, you initialize communication between your FPM and the RS-232 or RS-485
serial interface and then write to the interface. You can also read the properties of the data points
declared in the FPM driver in this routine.

• The OnTimer() routine handles timer expiration events. In the OnTimer() routine, you

initialize communication between your FPM and the RS-232 or RS-485 serial interface when a
timer started in the Initialize() routine expires. You can then read and write to the RS-232
or RS-485 interface, write updated values to the data point declared in the FPM driver, and read
the properties of the data points.

• The Shutdown() routine is executed when the FPM driver is stopped or disabled as a result of a

reboot. In the Shutdown() routine, you stop timers, close the RS-232 and RS-485 ports on the
SmartServer, and perform any required cleanup.

Note: The LonWorks\iLON\Development\eclipse\workspace.fpm directory on your computer
includes a sample RS-232 driver that you can view, edit, compile, and deploy on your SmartServer.

Writing the FPM Driver Initialize() Routine

The Initialize() routine is executed when the FPM driver is started or enabled. You can use this
routine to start timers; open the RS-232 or RS-485 serial interface on the SmartServer; and write to the
properties of the data points declared in the FPM driver.

• You can start timers using the Start()method of the CFPM_Timer class and the

START_TIMER()

macro as described in Writing the FPM Application Initialize() Routine.

• You can open the RS-232 serial interface using the rs232_open() method. You can open the

RS-485 serial interface using the rs485_open() method.

• You can set the default values, persistent flags, poll rates, and unit strings of the data points

declared in the FPM driver using the following collection of data point properties.

//write

data point default value in raw hex

Line1.SetDpProperty(FPM::Dp::cfgUCPTdefOutput,

nValue);

//set

whether data point is persistent