4.8.2 Status Output Functionality

Track Input

A Status Output configured for this function will indicate the current state of an input.

Track Output

A Status Output configured for this function will indicate the current physical state of a Safety Output, either ON or OFF.

Track Output’s Logical State

When selecting the Status Output function ‘Track output,’ an option to track the logical state, rather than the physical state, of a Safety
Output is provided. This option may be used to indicate a Safety Output has been commanded OFF, but is not OFF yet, such as during
an OFF-delay.

System Lockout Status

A Status Output configured for this function will be active when a lockout that affects the entire Safety Controller has been detected, such
as an internal memory fault.

I/O Fault Status

A Status Output configured for this function will be active when a lockout affecting a particular input or output has been detected, such as
a failed input or an EDM fault.

System Waiting for Reset

A Status Output configured for this function will be active under the following conditions:

• A system fault has occurred and all Safety Outputs are OFF.
• An EDM fault has occurred.
• An AVM fault has occurred.
• A fault on a Safety Output has occurred.
• A fault for monitoring a mute lamp has occurred.
• The Safety Controller is configured for manual reset on power-up.
• A fault on a THC input has occurred.

The following conditions involve the use of the system reset but no indication is provided by a Status Output:

• Exiting Configuration Mode
• Exiting Enable Mode
• Re-enabling a Track Input Group function of a Status Output

Output Waiting for Reset

A Status Output configured for this function will be active when a Safety Output is ready to be turned ON (a manual reset must be
performed).

Mute Status

A Status Output configured for this function will be active for a particular mutable Safety Input under the following conditions:

• ON during an active muting cycle.
• OFF during an inactive muting cycle.
• Flashing when all conditions for bypassing a mutable Safety Input (override) are present.
• ON when bypassing a mutable Safety Input.

Track Input Group

Status Outputs configured for this function will indicate which Safety Input of a defined group of Safety Inputs turned OFF first. Use a
system reset to re-enable the function after all Safety Inputs of the group are ON.