4.8 Status Outputs

4.8.1 Status Output Signal Conventions

Two signal conventions are selectable for each Status Output. The default convention provides a 24V dc signal when the monitored input
or output is active (closed, high or ON), when the system is in a Lockout, when there is an I/O-fault, when the system waits for a Reset,
when the output waits for a reset or during an active mute cycle. If the above conditions are not true, the signal output would show 0V.
Signal convention 2 is the reverse of convention 1, as shown in the following table.

Tracked Function

Mapped Status Output(s) State

Signal Convention 1 (default)

24V dc = Run

Signal Convention 2

0V dc = Run

Track Input

Input Run

Input Stop

Input Run

Input Stop

24V dc

0V dc

0V dc

24V dc

Track Output

Output ON

Output OFF

Output ON

Output OFF

24V dc

0V dc

0V dc

24V dc

System Lockout Status

Lockout

Run Mode

Lockout

Run Mode

24V dc

0V dc

0V dc

24V dc

I/O Fault

Fault

No Fault

Fault

No Fault

24V dc

0V dc

0V dc

24V dc

System Waiting for Reset Reset Required

Reset Not Required

Reset Required

Reset Not Required

24V dc

0V dc

0V dc

24V dc

Mute Status

Muted

No Mute

Muted

No Mute

24V dc

0V dc

0V dc

24V dc

Track Input Group

Input That Turned OFF
First

Other Linked Inputs

Input That Turned OFF
First

Other Linked Inputs

24V dc

0V dc

0V dc

24V dc

Bypass Status

Input Bypassed

Not Bypassed

Input Bypassed

Not Bypassed

24V dc

0V dc

0V dc

24V dc

Track Input Fault

Fault

No Fault

Fault

No Fault

24V dc

0V dc

0V dc

24V dc

OK to Cancel OFF-Delay

OK

Not OK

OK

Not OK

24V dc

0V dc

0V dc

24V dc

SC22-3/-3E Safety Controller Instruction Manual

50

www.bannerengineering.com - tel: 763-544-3164

P/N 133487 rev. C