8 status outputs, 1 status output signal conventions – Banner SC22-3E Safety Controller with Ethernet User Manual
Page 50
4.8 Status Outputs
4.8.1 Status Output Signal Conventions
Two signal conventions are selectable for each Status Output. The default convention provides a 24V dc signal when the monitored input
or output is active (closed, high or ON), when the system is in a Lockout, when there is an I/O-fault, when the system waits for a Reset,
when the output waits for a reset or during an active mute cycle. If the above conditions are not true, the signal output would show 0V.
Signal convention 2 is the reverse of convention 1, as shown in the following table.
Tracked Function
Mapped Status Output(s) State
Signal Convention 1 (default)
24V dc = Run
Signal Convention 2
0V dc = Run
Track Input
Input Run
Input Stop
Input Run
Input Stop
24V dc
0V dc
0V dc
24V dc
Track Output
Output ON
Output OFF
Output ON
Output OFF
24V dc
0V dc
0V dc
24V dc
System Lockout Status
Lockout
Run Mode
Lockout
Run Mode
24V dc
0V dc
0V dc
24V dc
I/O Fault
Fault
No Fault
Fault
No Fault
24V dc
0V dc
0V dc
24V dc
System Waiting for Reset Reset Required
Reset Not Required
Reset Required
Reset Not Required
24V dc
0V dc
0V dc
24V dc
Mute Status
Muted
No Mute
Muted
No Mute
24V dc
0V dc
0V dc
24V dc
Track Input Group
Input That Turned OFF
First
Other Linked Inputs
Input That Turned OFF
First
Other Linked Inputs
24V dc
0V dc
0V dc
24V dc
Bypass Status
Input Bypassed
Not Bypassed
Input Bypassed
Not Bypassed
24V dc
0V dc
0V dc
24V dc
Track Input Fault
Fault
No Fault
Fault
No Fault
24V dc
0V dc
0V dc
24V dc
OK to Cancel OFF-Delay
OK
Not OK
OK
Not OK
24V dc
0V dc
0V dc
24V dc
SC22-3/-3E Safety Controller Instruction Manual
50
www.bannerengineering.com - tel: 763-544-3164
P/N 133487 rev. C