Cancel OFF-Delay Devices. This feature provides the option to cancel a configured OFF-delay time. It functions in one of two ways:
• Keeps the Safety Output ON, or
• Turns the Safety Output OFF immediately, after the Controller receives a Cancel OFF-Delay signal.
A new Status Output (O.K. to Cancel Output's OFF-Delay Status) will indicate when a Cancel Delay Input can be activated, in order to
keep the OFF-delayed Safety Output ON.
Safety Input(s)
(Manual or Auto)
Cancel Delay Input
(Monitored Option Shown)
Safety Output
(Cancel Off Delay)
Status Output
(OK to Cancel OFF-Delay)
Off Delay
Started
Off Delay
Ended
Run
Stop
Run
Reset
Active
Inactive
ON
OFF
Off Delay
Normal End
Cancel Delay
Performed
Off Delay
0.5 sec.
2
2
1
1
Note 1 - If “turn output off” function is selected
Note 2 - If “keep output on” function is selected
Figure 11. Cancel Delay Timing: Safety Input remains in Stop mode