Cancel OFF-Delay Devices. This feature provides the option to cancel a configured OFF-delay time. It functions in one of two ways:

• Keeps the Safety Output ON, or
• Turns the Safety Output OFF immediately, after the Controller receives a Cancel OFF-Delay signal.

A new Status Output (O.K. to Cancel Output's OFF-Delay Status) will indicate when a Cancel Delay Input can be activated, in order to
keep the OFF-delayed Safety Output ON.

Safety Input(s)

(Manual or Auto)

Cancel Delay Input

(Monitored Option Shown)

Safety Output

(Cancel Off Delay)

Status Output

(OK to Cancel OFF-Delay)

Off Delay

Started

Off Delay

Ended

Run

Stop

Run

Reset

Active

Inactive

ON

OFF

Off Delay
Normal End

Cancel Delay
Performed

Off Delay

0.5 sec.

2

2

1

1

Note 1 - If “turn output off” function is selected

Note 2 - If “keep output on” function is selected

Figure 11. Cancel Delay Timing: Safety Input remains in Stop mode

Safety Input(s)

(Manual or Auto)

Cancel Delay Input

(Monitored Option Shown)

Safety Output

(Cancel Off Delay)

Status Output

(OK to Cancel OFF-Delay)

Off Delay

Started

Off Delay

Ended

Run

Stop

Run

Reset

Active

Inactive

ON

OFF

Off Delay
Normal End

On (Auto)

Off (Manual)

Cancel Delay
Performed

Off Delay

0.5 sec.

Figure 12. Cancel OFF-Delay Timing: "Turn Output OFF" function

SC22-3/-3E Safety Controller Instruction Manual

32

www.bannerengineering.com - tel: 763-544-3164

P/N 133487 rev. C