General parameter list – Rockwell Automation 2094-EN02D-M01-S1 Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual User Manual
Page 48

48
Rockwell Automation Publication 2094-RM001C-EN-P - May 2013
Chapter 5
General Device and Feedback Monitoring Configuration
General Parameter List
Set these parameters to configure general operation of the drive.
Table 16 - General Parameters
Tab
Parameter Name
Description
Values
(Safety Configuration Tool)
Safety
Change System
Configuration
System Configuration
Defines whether the drive is a single unit or if it occupies
a first, middle, or last position in a multi-axis cascaded
system.
Default:
Single Unit
Options:
Single Unit
Cascaded First Unit
Cascaded Middle Unit
Cascaded Last Unit
Operation Mode
Defines the primary operating mode of the speed
monitoring safety functions.
Default:
SafeStop
Options:
Disabled
SafeStop
SafeStop-DoorMonitor
SafeStop-SafeLimitedSpeed
SafeStop-SafeLimitedSpeed-DoorMonitor
SafeStop-SafeLimitedSpeed-EnableSwitch
SafeStop-SafeLimitedSpeed-DoorMonitor-EnableSwitch
SafeStop-SafeLimitedSpeedStatusOnly
Reset Type
Defines the type of reset used by the drive.
Default:
Manual Monitored
Options:
Automatic
Manual
Manual Monitored
Overspeed Response
Time
Configuration for the feedback interface sampling rate.
Default:
42 ms
Options:
42 ms
48 ms
60 ms
84 ms
132 ms
228 ms
420 ms