Rockwell Automation 2094-EN02D-M01-S1 Kinetix 6200 and Kinetix 6500 Safe Speed Monitoring Safety Reference Manual User Manual
Page 148
148
Rockwell Automation Publication 2094-RM001C-EN-P - May 2013
Appendix B
Parameter Data
Input
Change Input
Configuration Type
Door Monitor
Configuration for the Door Monitor input (DM_In).
Default:
Not Used
Lock Monitor
Configuration for the Lock Monitor input (LM_In).
Options:
Not Used
Dual Channel Equivalent
Dual Channel Equivalent 3 s
Dual Channel Complementary
Dual Channel Complementary 3 s
Solid State Device Equivalent 3 s
Single Channel
Safe Limited Speed
Configuration for the Safe Limited Speed input
(SLS_In).
Enabling Switch
Monitor
Configuration for the Enabling Switch input (ESM_In).
Safe Stop
Change Safe Stop
Configuration
Stop Category
Safe operating stop type selection. This defines the type
of Safe Stop that is performed if the Safe Stop function
is initiated by a stop type condition.
Default:
Safe Torque-Off
Options:
Safe Torque-Off
Safe Stop 1
Safe Stop 2
Enable Standstill Checking.
Automatically enabled for Safe Stop 1 and Safe Stop 2.
Default:
Standstill Checking Enabled
Options:
Standstill Checking Enabled
Standstill Checking Not Enabled
Safe Stop Monitor
Delay
Defines the monitoring delay between the request and
the Maximum Stop Time when the request for a Safe
Stop 1 or a Safe Stop 2 is initiated by an SS_In input ON
to OFF transition.
If the Stop Category is Safe Torque-Off with or without
Standstill Speed Checking, the Safe Stop Monitor Delay
must be 0 or an Invalid Configuration fault occurs.
Default:
0
Range:
0
…
6553.5 s
Deceleration
Reference Speed
Determines deceleration rate to monitor for Safe Stop 1
or Safe Stop 2.
Default:
0
Range:
0
…
65,535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter
Maximum Stop Time
Defines the maximum stop delay time that is used when
the Safe Stop function is initiated by a stop type
condition.
Default:
0
Range:
0
…
6553.5 s
Deceleration
Tolerance
This is the acceptable tolerance above the deceleration
rate set by the [Deceleration Reference Speed]
parameter.
Default:
0
Range:
0
…
100% of Deceleration Reference Speed
Standstill Speed
Defines the speed limit that is used to declare motion as
stopped.
Not valid for Safe Torque-Off without Standstill
Checking.
Default:
0.001
Range:
0.001
…
65.535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter
Standstill Position
Window
Defines the position limit window in encoder 1 degrees
or mm that is tolerated after a safe stop condition has
been detected.
Not valid for Safe Torque-Off without Standstill
Checking.
Default:
10
Range:
0
…
65,535 degrees (360° = 1 revolution) or mm
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter
Safe Limited Speed
Change Safe Limited
Speed Configuration
Safe Limited Speed
Monitor Delay
Defines the Safe Limited Speed Monitoring Delay
between the SLS_In ON to OFF transition and the
initiation of the Safe Limited Speed (SLS) monitoring.
Default:
0
Range:
0
…
6553.5 s
Safe Speed Limit
Defines the speed limit that is monitored in Safe Limited
Speed (SLS) mode.
Default:
0
Range:
0
…
65,535 rpm or mm/s
ratio based on revolutions or millimeters configuration
defined by the [Primary Feedback Units] parameter
Table 41 - Configurable Parameters and Settings (continued)
Tab
Parameter Name
Description
Values
(Safety Configuration Tool)