6 - configure local i/o, Introduction, Configure local safety inputs – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual
Page 67: Chapter 6, Configure local i/o, Introduction configure local safety inputs, Chapter

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014
67
Chapter
6
Configure Local I/O
Introduction
Configure Local Safety Inputs
The controller has 16 local safety inputs that support the following features.
•
Input circuit diagnosis — Test pulse sources can be used to monitor
internal circuits, external devices, and external wiring.
•
Input on- and off-delays — You can set input time filters of 0...126 ms in
multiples of the controller cycle time. Setting input on- and off-delays
helps reduce the influence of chattering and external noise.
•
Dual Channel mode — You can set Dual Channel mode for pairs of
related local inputs. When Dual Channel mode is set, time discrepancies in
data changes or input signals between two paired local inputs can be
evaluated.
Follow these steps to configure local safety inputs.
1.
Right-click the SmartGuard controller and choose Properties.
Topic
Page
Configure Local Safety Outputs
IMPORTANT
Input on- and off-delays must be added to the I/O response time. This
will affect the system reaction time calculations.
Refer to SmartGuard Controllers Safety Reference Manual, publicatio
1752-RM001