beautypg.com

Light curtain function block timing chart, Safety gate monitoring function block – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual

Page 225

background image

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014

225

Function Blocks Command Reference

Appendix D

Use this table to diagnose and reset a discrepancy error condition in the LC
function block.

Light Curtain Function Block Timing Chart

The chart shows the I/O timing when the function block is set up as Dual
Channel Equivalent.

Safety Gate Monitoring
Function Block

Figure 52 - Safety Gate Monitoring Function Block Diagram

The Safety Gate Monitoring function monitors the status of a safety gate, by
using input signals from a safety door switch or safety limit switch connected to
the door. The Output Enable signal turns on if the inputs from the switch being
monitored are active. The Output Enable signal turns off if the inputs become
inactive or if an error is detected for that function block.

Table 15 - Error Detection and Reset for LC Function Block

Error

Condition

Status When an Error Occurs

To Reset the Error Condition

Output Enable

Fault

Present

Error Output

Discrepancy
Error

OFF
(Safety State)

ON

Discrepancy
Error Output:
ON

Remove the cause of the error and then
either:
1. Make the inputs inactive and active

again.

2. Change the controller’s operating

mode to Idle and back to Run.

Input 1 (NC)

Input 2 (NC)

Fault Present

Idle to Run

Output Enable

Discrepancy

Error

Discrepancy Time

!

!

!
!

!

Input 1

(pair 1 - NC)

Output
Enable

Output Enable

Discrepancy Error (pair 1)

Default Connections

Maximum I/O for Safety Gate Function

Input 2

(pair 1 - NC)

Input 1 (pair 1 - NC)

Input 2 (pair 1 - NC)

Input 3 (pair 2 - NC)

Input 4 (pair 2 - NC)

Function Test Signal

Discrepancy Error (pair 2)
Function Test Required
Synchronization Error

Function Test Error

Fault Present

This manual is related to the following products: