Edm function block fault present output setting, Edm function block parameter, Edm function block error handling – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual
Page 237

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014
237
Function Blocks Command Reference
Appendix D
Block Properties dialog box in the Logic Editor of RSNetWorx for DeviceNet
software.
•
EDM error
•
Output 2
EDM Function Block Fault Present Output Setting
The Fault Present output can also be used in programming. To enable this
output, check the Use Fault Present checkbox on the Out point tab of the
Function Block Properties dialog box.
EDM Function Block Parameter
Set this parameter for the EDM function block.
EDM Function Block Error Handling
Use this table to diagnose and reset a discrepancy error condition in the EDM
function block.
Table 26 - EDM Function Block Parameter
Parameter
Range
Default
EDM Feedback Maximum Time Delay (T
EDM
)
100…1000 ms in 10 ms increments
300 ms
Table 27 - Error Detection and Reset for EDM Function Block
Error
Condition
Status When an Error Occurs
To Reset the Error Condition
Output Enable
Fault
Present
Error Output
EDM Feedback
Error
OFF
(Safety State)
ON
EDM Error
Output: ON
Remove the cause of the error and turn
ON the safety input.