Routing instruction, Routing instruction diagram, Routing instruction truth table – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual
Page 211: Reset set flip-flop (rs-ff) instruction, Reset set flip-flop instruction diagram

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014
211
Logic Functions Command Reference
Appendix C
Routing Instruction
The Routing instruction routes one input signal to a maximum of eight output
signals. It is used to output a signal to more than one physical address, such as an
output tag. The number of outputs can be set by using the I/O Setting tab in the
Function Block Properties dialog box. The default setting is one.
Routing Instruction Diagram
Routing Instruction Truth Table
In the truth table, 0 is off and 1 is on.
Reset Set Flip-flop (RS-FF)
Instruction
When the input signal is on, the Output Enable signal is turned on. The Output
Enable signal stays on even if the input signal turns off. When the Reset signal is
on, the Output Enable signal turns off.
A Fault Present output can also be used in programming. To enable this optional
output, check the Use Fault Present checkbox on the I/O Settings tab of the
Function Block Properties dialog box in RSNetWorx for DeviceNet software.
Reset Set Flip-flop Instruction Diagram
Output 1
Input 1
Table C.3 Truth Table for Routing Evaluation
Input 1
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
!
Output Enable
Input
Reset
Default Connections
Maximum Inputs for Reset Set Flip-Flop Function
Output Enable
Input
Reset
Fault Present