Download and Verify
Follow these steps to download the DeviceNet network configuration.
1.
Go online by clicking the online
icon.
2.
Browse to the DeviceNet network and click OK at the prompt.
During each browse operation, RSNetWorx for DeviceNet software reads
the following attributes of each device.
3.
Download your configuration to the network by right-clicking the device
and choosing Download to Device.
4.
Confirm your intent to download by clicking Yes.
If a device is password-protected, RSNetWorx for DeviceNet software
prompts you to type the password for each protected device.
If a device is safety-locked, you must first unlock the device and then
download.
Safety Attribute
Description
Safety Network Number (SNN)
and Node Address Combination
The node address and SNN stored in the RSNetWorx for DeviceNet
configuration file must match the node address and SNN of the online
device. If the SNNs do not match, the device enters the SNN error state.
See page 65 for information on resolving an SNN mismatch error.
Configuration Signature
RSNetWorx for DeviceNet software compares the configuration
signature in its configuration file with the configuration signature in the
online device.
Safety-Lock
If the device is safety-locked, its configuration cannot be modified
without first unlocking the device.
IMPORTANT
If you safety-unlock a device, you must run the Safety Device
Verification Wizard to re-verify and safety-lock the device before
operating the device in your safety system.
TIP
If none of your devices are password-protected or safety-locked, you
can choose Download to Network from the Network menu to download
your configuration to the network. However, this process skips devices
that are password-protected or safety-locked.