The Output Enable signal turns on if the Reset signal is correctly received while
the Monitored Input condition to the Reset function block is on. This function
block can be used to prevent the machine from automatically resetting when
power to the controller is turned on, when the operating mode is changed from
Idle mode to Run mode, or when a signal from a safety input device turns on.
The Static Release and Reset Required Indication are optional outputs. To enable
either of these outputs, check the checkbox on the Out point tab of the Function
Block Properties dialog box.
Reset Function Block Parameters
You can set the Reset signal for either Low-High-Low or Rising Edge by using the
Parameter tab of the Function Block Properties dialog box. The default setting is
Low-High-Low.
When configured for Low-High-Low, the Reset signal must meet the following
conditions.
Table 8 - Conditions for Outputs Turning On
Output
Condition for Turn-on
Output Enable
The Monitored Input and all enabled optional inputs must be ON, and
the Reset signal must be received correctly.
Static Release
The Monitored Input and all enabled optional inputs must be ON.
Reset Required Indication
The Reset Required Indication becomes a 1 Hz pulse output if the
Monitored Input and all enabled optional inputs are ON, and the Output
Enable signal is OFF.
The Reset Required Indication turns ON only when the Reset signal is
ON.
350 ms min