Appendix E
Explicit Messages
Read Monitor
Status of Output
Total On Time or
Contact
Operation
Counter
Read
Reads the monitor status of
the total on time or contact
operation counter for the
output (1…8) specified by the
Instance ID.
0E hex
3B hex
01…08 hex
67 hex
—
1 byte
00 hex: in range
01 hex: out of range (over
monitor value)
Read Safety
Output Normal
Flag
Read
Reads the normal flag status of
the number (1…8) specified
by the Instance ID.
0E hex
3B hex
01…08 hex
05 hex
—
1 byte
00 hex: error
01 hex: normal
Read Safety
Output Error
Information
Cause
Read
Reads the cause for the normal
flag of the number (1…8)
specified by the Instance ID
being off (error).
0E hex
3B hex
01…08 hex
6E hex
—
1 byte
00 hex: no error
01 hex: invalid configuration
02 hex: overcurrent detection
03 hex: short-circuit detection
04 hex: high constant error
05 hex: error in either of dual
channels
06 hex: internal relay circuit
error
07 hex: relay error
08 hex: data error between
dual channel outputs
09 hex: detection of short-
circuit between wires
Read AND of
Safety Output
Normal Flags
Read
Reads the cause for the normal
flag of the number (1…8)
specified by the Instance ID
being off (error).
0E hex
3C hex
01 hex
05 hex
—
1 byte
00 hex: error
01 hex: all normal
Read OR of
Monitor Status of
Output Total On
Times or Contact
Operation
Counters
Read
Reads the logical OR of the
monitor status of the total on
time or contact operation
counter for all outputs 1…8.
0E hex
3C hex
01 hex
72 hex
—
1 byte
00 hex: all in range
01 hex: input out of range
(over monitor value)
Table 43 - Setting and Monitoring Safety Output Terminals
Explicit
Message
Service
Function
Command
Response
Service
Code
Class
ID
Instance ID
Attribute
ID
Data Size
Table 44 - Monitoring Test Output Terminals
Explicit
Message
Service
Function
Command
Response
Service
Code
Class
ID
Instance ID
Attribute
ID
Data Size
Monitor Mode for
Terminal
Maintenance
Information
Read
Reads the monitor mode of
maintenance information for the
test output (1…4) specified by
the Instance ID.
0E hex
35B hex
01…04 hex
83 hex
—
1 byte
00 hex: Total On Time
mode
01 hex: Contact Operation
Counter mode
Write
Writes the monitor mode of
maintenance information for the
test output (1…4) specified by
the Instance ID.
10 hex
35B hex
01…04 hex
83 hex
1 byte
00 hex: Total On
Time mode
01 hex: Contact
Operation Counter
mode
—