EDM Function Block Timing Chart
Muting
Figure 61 - Muting Function Block Diagrams
The Muting function block temporarily disables the light-interruption signal
(AOPD input) in a light curtain while the muting sensor is being triggered.
While the muting function is operating, machine operation is not stopped, so an
object can be removed from the light curtain’s detection zone. In addition, the
Muting function block has an override function that can disable the light-
interruption signal of the light curtain and cause the machine to operate while
the light of the light curtain is obstructed. For example, when an object has
stopped in the light curtain’s detection zone, the machine can be operated in
order to remove the object.
Monitored
Input
Idle
to Run
EDM Feedback
Output 1
Output 2
EDM Error
T
EDM
Fault Present
T
EDM
T
EDM
T
EDM
T
EDM
!
!
!
!
!
S12
S11
AOPD Input 1 (NC)
Output Enable
Default Connections
Maximum I/O for Muting Function
Fault Present
AOPD Input 2 (NC)
Muting Signal 11
Muting Signal 12
AOPD Input 1 (NC)
AOPD Input 2 (NC)
Override Input 1 (NC)
Override Input 2 (NC)
Muting Signal 11
Muting Signal 12
Muting Signal 21
Muting Signal 22
Muting
Overriding
Sequence Error
Synchronization Error
Discrepancy Error (AOPD)
Discrepancy Error (Override)