14 the l_s8v_drive82vector.lib library, The l_s8v_drive82vector.lib library, Plc designer v2.x| lenze application samples – Lenze PLC Designer V2.x User Manual
Page 267
1.3 EN - 07/2012
L
267
PLC Designer V2.x| Lenze Application Samples
The L_S8V_Drive82Vector.lib library
L_S8V_ActuatorSpeed - actuation of the 8200 vector controller
14
The L_S8V_Drive82Vector.lib library
This chapter describes the function blocks of the L_S8V_Drive82Vector function library.
The function blocks of this function library serve to parameterise the 8200 vector Lenze
frequency inverter.
14.1
L_S8V_ActuatorSpeed - actuation of the 8200 vector controller
This FB serves as a control block for the 8200 vector.
Inputs
Outputs
Further information on the controller can be found in the following
documentation:
• System manual (SHB) 8200 vector - Global Drive
Identifier/data type
Information/possible settings
scDriveControl
Structural data for drive control
xOptional
BOOL
Optional setting for the CAN node
FALSE Normal operation (transmission and reception via PDO)
TRUE The CAN node is set to the "Optional" mode to be able to receive
PDOs.
byNodeNumber
BYTE
Node number
byMasterNumber
BYTE
Interface number (0...3)
Identifier/data type
Information/possible settings
scDriveStatus
Structural data regarding the drive status
xInternalControlActiv
BOOL
TRUE: Internal control active