Plc designer v2.x| lenze application samples – Lenze PLC Designer V2.x User Manual
Page 248
PLC Designer V2.x| Lenze Application Samples
The L_S94_Drive9400.lib library
L_S94_ActuatorSpeed - actuation of the 9400 HighLine controller
248
L
1.3 EN - 07/2012
12.1.2
Structure of S94_DriveStatus_ActSpeed - status of the controller
Further information on the internal interfaces of the controller can be found in
the software manual (SW) 9400 HighLine controller under the corresponding
basic drive function.
Identifier/data type
Control bits in the controller
Bit
Identifier
Meaning
xDriveError
BOOL
1
DI_bFailActive
Status signal "Error active -
acknowledgement required"
xDriveReady
BOOL
0
DI_bReady
Status signal "Controller is ready for
operation"
xDriveEnabled
BOOL
2
DI_bOperationEnabled
Status signal "Operation is enabled"
xSpeedEqZero
BOOL
4
MI_bSpeedBelowThresholdC19
Status signal "Standstill reached"
(observe speed value in code 19)
xQSPActive
BOOL
3
QSP_bActive
Status signal "Quick stop through
application active"
xSpeedFollowerActive
BOOL
5
HM_bEnable
Request control of basic function
xManualJogActive
BOOL
6
MAN_bActive
Status signal "Basic function is active"
xWarningActive
BOOL
7
DI_bWarningActive
Status signal "Warning active"
xDI_EnableNotOk
BOOL
11
DIGIN_bCInh
Status signal "Controller inhibit"
xDI_Digin1
BOOL
12
DIGIN_bIn1
Digital input 1
xDI_Digin2
BOOL
13
DIGIN_bIn2
Digital input 2
xDI_Digin3
BOOL
14
DIGIN_bIn3
Digital input 3
xDI_Digin4
BOOL
15
DIGIN_bIn4
Digital input 4
rNact
REAL
MI_dnActualMotorSpeed_n
Current speed of the motor shaft in [%]
0 ... 199.99 %
rMact
REAL
MI_dnFilteredTorqueSetpoint_n Filtered torque setpoint (after jerk
limitation and band-stop filters)
0 ... 199.99 %
xCommunicationOK
BOOL
L_SCB_GetNodeDataRxPDO1 - read out data ( 285)
L_SCB_GetNodeDataRxPDO2 - read out data ( 286)
xOptional
L_SCB_GetStateOptional - check with regard to "OptionalDevice" ( 287)
xFreeBit08
8
Not assigned
xFreeBit09
9
Not assigned
xFreeBit10
10
Not assigned
eCanNodeState
SCB_StateCanNode
SCB_StateCanNode