Operation

Power Supply Operation

Release 3.0

69

To set the Under-Current Protection:

To set the Over-Power Protection:

Step # Do This

You Will See

1

OVP SET 0V

2

Press repeatedly until the

desired setting appears.

UCP SET 0A

3

UCP SET 0A

4

Use the Current knob, the numeric
keypad, or the arrow keys to enter a
value. The value must be between
0–103% of the unit’s rated current.

UCP SET ####A

5

S/D if trip? N

6

Use the arrow keys to select Yes or No.

For this example, Yes is selected.

S/D if trip? Y

7

This setting is saved and the display
returns to its default operating mode.

Step # Do This

You Will See

1

OVP SET 0V

2

Press repeatedly until the

desired setting appears.

OPP SET 0W

3

OPP SET 0W

4

Use both the Current and Voltage
knobs, or the numeric keypad, or the
arrow keys to enter a value. The
value must be between 0W and
103% of the unit’s rated power.

OPP SET ####W

5

S/D if trip? N

6

Use the arrow keys to select Yes or
No. For this example, Yes is selected.

S/D if trip? Y

7

This setting is saved and the display
returns to its default operating mode.

PROT SET

ALARMS

PROT SET

ALARMS

ENTER

ENTER

ENTER

PROT SET

ALARMS

PROT SET

ALARMS

ENTER

ENTER

ENTER