beautypg.com

Table e.8 – Xantrex Technology XDC User Manual

Page 237

background image

Specifications and Characteristics

Electrical Specifications—Summary

Release 3.0

235

Table E.8Drift Specifications for 12000 Watt units (80V to 600V Models)

Models

80–150

100–120

150–80

300–40

600–20

Drift (30 minutes):

1

Voltage (0.04% of Vmax)
Current (0.6% of Imax)

1. Maximum drift over 30 minutes with constant line, load, and temperature, after power on.

32 mV
900 mA

40 mV
720 mA

60 mV
480 mA

120 mV
240 mA

240 mV
120 mA

Drift (8 hours):

2

Voltage (0.02% of Vmax)
Current (0.05% of Imax)

3

2. Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.
3. Current drift for 600V-20A unit is 0.08% of Imax.

16 mV
75 mA

20 mV
60 mA

30 mV
40 mA

60 mV
20 mA

120 mV
16 mA

Temperature Coefficient:

4

Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)

4. Change in output per

°C change in ambient temperature, with constant line and load.

32 mV
90 mA

40 mV
72 mA

60 mV
48 mA

120 mV
24 mA

240 mV
12 mA