Table e.8 – Xantrex Technology XDC User Manual
Page 237
Specifications and Characteristics
Electrical Specifications—Summary
Release 3.0
235
Table E.8Drift Specifications for 12000 Watt units (80V to 600V Models)
Models
80–150
100–120
150–80
300–40
600–20
Drift (30 minutes):
1
Voltage (0.04% of Vmax)
Current (0.6% of Imax)
1. Maximum drift over 30 minutes with constant line, load, and temperature, after power on.
32 mV
900 mA
40 mV
720 mA
60 mV
480 mA
120 mV
240 mA
240 mV
120 mA
Drift (8 hours):
2
Voltage (0.02% of Vmax)
Current (0.05% of Imax)
3
2. Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.
3. Current drift for 600V-20A unit is 0.08% of Imax.
16 mV
75 mA
20 mV
60 mA
30 mV
40 mA
60 mV
20 mA
120 mV
16 mA
Temperature Coefficient:
4
Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)
4. Change in output per
°C change in ambient temperature, with constant line and load.
32 mV
90 mA
40 mV
72 mA
60 mV
48 mA
120 mV
24 mA
240 mV
12 mA