beautypg.com

Last setting, User setting, Auto sequence – Xantrex Technology XDC User Manual

Page 126

background image

Remote Operation
SCPI Commands for Digital Interfaces

124

Operating Manual for XDC Series Power Supply

Last Setting

Selecting Last Setting lets you restore the settings that are in use when the power
supply is powered off, the next time it is powered on.

To power on the last stored setting:
OUTP:PON:REC LAST

To check the current user setting:
OUTP:PON:REC?

The response should be LAST.

User Setting

Selecting User Setting lets you restore a custom setting next time the unit is powered
on. This assumes that at least one user setting has been set up and stored in memory.
See “Store User Settings” on page 77.

To power on user setting #1:
OUTP:PON:REC USER1

To check the setting:
OUTP:PON:REC?

The response should be USER1.

The user setting must be in the range of 1–10. See “Store User Settings” on page 127
for an explanation of how to save user settings.

Auto Sequence

Selecting Auto Sequence lets you recall a stored program next time the unit is
powered ON. This assumes that at least one program has been created and stored in
memory. See “Editing Trigger Source of a Sequence” on page 96 for more
information. See for information about remotely programming and running auto
sequence programs.

To reset to user setting #1:
OUTP:PON:REC SEQ1

To check the setting:
OUTP:PON:REC?

The response should be SEQ1.