beautypg.com

Canbus error codes, Multichannel error codes, Canbus error codes multichannel error codes – Xantrex Technology XDC User Manual

Page 223: Table c.11, Table c.12

background image

Error Messages

CANbus Error Codes

Release 3.0

221

CANbus Error Codes

Table C.11CANbus Error Codes

Multichannel Error Codes

Multichannel functionality is only available with the 6000 Watt power supply.

Table C.12Multichannel Error Codes

Error
code

Error Message Description

+1701 CANbus hardware missing

The CANbus option is not installed on the controller card, or controller card is
not present.

+1702 CANbus device specific error

An error has occurred on the CANbus circuit. Probable causes are AC input
too low, AC input not secure, controller card not securely fastened or other
noise sources.

+1703 CANbus input buffer corrupted.
+1704 CANbus input buffer corrupted.
+1705 CANbus input buffer overrun.

Data is sent on the CANbus faster than the CPU can process.

+1706 CANbus output buffer overrun.

Data cannot be transmitted fast enough.

Error
code

Error Message Description

+1800 Multichannel general error

An error has occurred while sending multichannel commands. One such
cause is sending a command that is too long.

+1802 Multichannel address taken

The multichannel address configured for this unit has already been assigned
to another unit on the CANbus network.

+1803 Multichannel originator not responding

The originator of the message is not responding to the handshaking.

+1804 Multichannel recipient not responding

The recipient of the message is not acknowledging the reception of the
command.

+1805 Multichannel command overwritten

A received command through the CANbus has been overwritten.