beautypg.com

Table e.5 – Xantrex Technology XDC User Manual

Page 234

background image

Specifications and Characteristics
Electrical Specifications—Summary

232

Operating Manual for XDC Series Power Supply

Table E.5Specifications for 12000 Watt units (10V to 60V Models)

Models

10-1200

20-600

30-400

40-300

60-200

Output Ratings:

Output Voltage

1

Output Current

2

Output Power

1. Minimum output voltage is <0.3% of rated voltage at zero output setting.
2. Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.

0–10 V
0–1200 A
12000 W

0–20 V
0–600 A
12000 W

0–30 V
0–400 A
12000 W

0–40 V
0–300 A
12000 W

0–60 V
0–200 A
12000 W

Line Regulation:

3

Voltage

(0.01% of Vmax)

Current (0.1% of Imax)

3. For input voltage variation over the AC input voltage range, with constant rated load.

1 mV
1200 mA

2 mV
600 mA

3 mV
400 mA

4 mV
300 mA

6 mV
200 mA

Load Regulation:

4

Voltage (0.05% of Vmax + 5 mV)
Current (0.2% of Imax + 40 mA)

4. For 0–100% load variation, with constant nominal line voltage.

10 mV
2440 mA

15 mV
1240 mA

20 mV
840 mA

25 mV
640 mA

35 mV
440 mA

Meter Accuracy:

Voltage (0.15% of Vmax)
Current (0.5% of Imax)

15 mV
6 A

30 mV
3 A

45 mV
2.0 A

60 mV
1.5 A

90 mV
1 A

Output Noise (0–20 MHz):

Voltage (p–p)

75 mV

75 mV

75 mV

75 mV

100 mV

Output Ripple (rms):

Voltage
Current

5

5. Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.

10 mV
6200 mA

10 mV
3200 mA

12 mV
2000 mA

15 mV
1500 mA

15 mV
900 mA

OVP Adjustment Range:

(0% to 103% of Vmax)

0–10.3 V

0–20.6 V

0–30.9 V

0–41.2 V

0–61.8 V

Efficiency:

6

6. Typical efficiency at nominal input voltage and full output power.

0.85

0.87

0.87

0.87

0.89