Operation

Power Supply Operation

Release 3.0

101

To set the current limits:

Step # Do This

You Will See

1

ERROR MSGS

2

until you see the “SETPT

LIMIT” option

SETPT LIMIT

3

Voltage Limit

4

Current Limit

5

High 0A

6

Use the Current knob, arrow keys, or
numeric keypad to enter a value. The
value must be within 0A to 103% of
the unit’s rated current.

High #####A

7

Low 0A

The Maximum setting is saved and
the Minimum setting appears.

8

Use the Voltage knob, arrow keys, or
numeric keypad to enter a value. The
value must be within 0A to 103% of
the unit’s rated current.

Low #####A

9

The setting is saved and the display
returns to its default operating mode.

MENU

ENTER

ENTER

ENTER

ENTER