beautypg.com

Configuration, Front panel, Select the "remote config" menu – Xantrex Technology XDC User Manual

Page 116: Select the "multichnl cfg" menu. press enter, Scpi, Setup, Configuration setup

background image

Remote Operation
Multichannel Operation (6000 Watt only)

114

Operating Manual for XDC Series Power Supply

Configuration Before connecting a power supply to a multichannel network, you must configure

each power supply with a unique address. The front panel or a remote interface
maybe used to do this.

One power supply must be configured to operate via RS-232 or GPIB.

Front Panel

1. Select the "REMOTE CONFIG" menu
2. Select the "Multichnl Cfg" menu. Press ENTER.
3. When prompted with "Addr" enter a unique network address in the range 1–50.

Press ENTER

To receive and execute commands:

1. Select the "REMOTE SELECT" menu, then select "Multichannel" from the

list. Press ENTER.

SCPI

Set a slave's multichannel address using the command:
SYSTem:COMMunicate:MCHannel:ADDRess

where multichannel-address is an integer in the range of 1-50, and the command is
sent via a controller directly connected to the slave’s RS-232 port.

If the unit is to execute commands, set the power supply to accept control via
multichannel commands (the CANbus interface) with the SCPI command:
SYSTem:REMote:SOURce MCHannel

Setup 1. Connect power supplies to be controlled via the CANbus network. Parallel male

DB9 to female DB9 cables (N-1) are required. Connect the power supplies in
series, linking the first power supply to the second using one cable, and then the
second to the third using a second cable and the second CAN port. A single
ribbon cable with multiple connectors may be used instead of several cables for
ease of connection. Terminate the bus at both ends with 120 ohm, 1/4 Watt
resistors (included) across the CAN HI and CAN LO signals (Pins 2 and 7). See
Table 4.5, “CANbus Pins,” on page 113.