Specifications and Characteristics

Output Performance Specifications

Release 3.0

237

Output Performance Specifications

These specifications define the electrical performance specifications of the power
supply output. These specifications apply to both local and remote sense
configurations, except where noted. These specifications apply to all programming
sources, except where noted.

Rated Output Range

Efficiency

Typical 89% efficiency at nominal line voltage and ambient temperature.

Minimum 82% efficiency. Specific minimum efficiency limits are model
dependent.

Load Regulation

Line Regulation

Programming Range for Voltage, Current, and Power

OVP Programming Range

0–103% of maximum rated voltage

Voltage

0–100%

Current

0–100%

Voltage

5 mV + 0.05% of Vmax

Current

6000 W: 20 mA + 0.1% of Imax
12000 W: 40 mA + 0.2% of Imax

Power

1% of Pmax

Voltage

0.01% of Vmax

Current

6000 W: 0.05% of Imax
12000 W: 0.1% of Imax

Power

1% of Pmax

Voltage and Current

From 0–103% of the rated maximum output

Power

From 3–103% of the rated maximum output