15. ABSOLUTE POSITION DETECTION SYSTEM

3) ABS transfer mode finish-time time-out check

If the ABS transfer mode (ABSR) is not turned OFF within 5s after the last ready to send signal
(19th signal for ABS data transmission) is turned ON, it is regarded as the transmission error
and the ABS time-out warning (AL.E5) is output.

OFF

ON

OFF

ON

OFF

ON

1

2

3

4

18

19

1

2

3

4

18

19

5s

ABS transfer mode

ABS request

Send data ready

AL.E5 warning

Signal is not turned OFF

No

Yes

(b) Check sum error

If the check sum error occurs, the programmable controller should retry transmission of the ABS
data.
Using the ladder check program, turn OFF the ABS transfer mode (ABSM) and servo-on (SON)
once. Turn them ON again after an OFF time of longer than 20 ms.
If the ABS data transmission fails to end normally even after retry, regard this situation as an
ABS check sum error and execute error processing.
The start command should be interlocked with the ABS data ready signal to disable positioning
operation when an check sum error occurs.

OFF

ON

OFF

ON

OFF

ON

OFF

ON

Servo-on

ABS transfer mode

ABS request

Send data ready

ABS check sum error

20ms

or more

20ms

or more

20ms

or more

Retry 1

Retry 2

Retry 3

No

Yes