13 - 47

13. OPTIONS AND AUXILIARY EQUIPMENT

(b) Surge suppressor

The recommended surge suppressor for installation to an AC relay, AC valve, AC electromagnetic
brake or the like near the servo amplifier is shown below. Use this product or equivalent.

Relay

This distance should be short

(within 20cm(0.79 in.)).

Surge suppressor

MC

Surge suppressor

Surge suppressor

(Ex.) 972A.2003 50411

(Matsuo Electric Co.,Ltd. 200VAC rating)

Outline drawing [Unit: mm] ([Unit: in.])

Rated

voltage

AC[V]

C [ F]

R [

]

Test voltage AC[V]

200

0.5

50

(1W)

Across

T-C 1000(1 to 5s)

Blue vinyl cord

Red vinyl cord

Vinyl sheath

200(7.87)

or more

200(7.87)

or more

6(0.24)

31(1.22)

10(0.39)or less

10(0.39)or less

15 1(0.59 0.04)

48 1.5

(1.89 0.06)

10 3
(0.39
0.15)

10 3
(0.39
0.12)

4(0.16)

18 1.5

(0.71 0.06)

Note that a diode should be installed to a DC relay, DC valve or
the like.

Maximum voltage: Not less than 4 times the drive voltage of

the relay or the like

Maximum current: Not less than twice the drive current of

the relay or the like

Diode

RA

(c) Cable clamp fitting (AERSBAN -SET)

Generally, the earth of the shielded cable may only be connected to the connector's SD terminal.
However, the effect can be increased by directly connecting the cable to an earth plate as shown
below.
Install the earth plate near the servo amplifier for the encoder cable. Peel part of the cable sheath
to expose the external conductor, and press that part against the earth plate with the cable clamp.
If the cable is thin, clamp several cables in a bunch.
The clamp comes as a set with the earth plate.

Strip the cable sheath of
the clamped area.

cutter

cable

Cable clamp

(A,B)

Cable

Earth plate

External conductor

Clamp section diagram

40

(1

.57)