Options and auxiliary equipment, 2) connection example – MITSUBISHI ELECTRIC MELSERVO MR-J2S- A User Manual
Page 238
13 - 13
13. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
Power supply
3-phase
200V or 230VAC
NFB
MC
Servo amplifier
L
11
L
21
L
1
L
2
L
3
SK
ON
MC
B
C
RDY
SE
Alarm
output
RDY
output
A
B
C
Operation ready
MC
OFF
EMG
RA2
FR-RC
Ready
(Note3)Power factor improving reactor
FR-BAL
R/L
1
S/L
2
T/L
3
B
C
EMG
SON
SG
COM
ALM
VDD
RA2
R
RX
R
SX
S
TX
T
Phase detection
terminals
(Note 1)
Power regeneration
converter FR-RC
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain removed,
the FR-RC will not operate.
2. For the servo amplifiers of 5k and 7kW, always remove the wiring (across P-C) of the built-in regenerative brake resistor.
3. Refer to the power return converter FR-RC instruction manual (IB(NA)-66330) for the power factor improving reactor to be used.
When using FR-RC with the servo amplifier of 11k to 22kW, do not use the power factor improving reactor (FR-BEL) together.
4. For the amplifiers of 11k to 22kW, always connect across P-P1. (Wiring is factory-connected.)
N
P
5m(16.4ft) or less
N/
P/
(Note2)
C
P
1
(Note4)