14. COMMUNICATION FUNCTIONS

14.9 Initialization

After the slave station is switched on, it cannot reply to communication until the internal initialization
processing terminates. Hence, at power-on, ordinary communication should be started after:
(1) 1s or more time has elapsed after the slave station is switched on; and
(2) Making sure that normal communication can be made by reading the parameter or other data which

does not pose any safety problems.

14.10 Communication procedure example

The following example reads the set value of parameter No.2 "function selection 1" from the servo
amplifier of station 0:

Data item

Value

Description

Station number

0

Servo amplifier station 0

Command

05

Read command

Data No.

02

Parameter No.2

Checksum 30H 30H 35H 02H 30H 32H 03H FCH

0 2

STX

ETX

5

0

Yes

No

Yes

No

No

No

Yes

Yes

Yes

No

[0][0][5] [0][2]

[0]

Axis No. Command

Data No.

Data

Start

Data make-up

Checksum calculation and
addition

Addition of SOH to make
up transmission data

Data transmission

Data receive

Is there receive data?

3 consecutive times?

Error processing

Other than error code

[A] [a]?

Receive data analysis

End

300ms elapsed?

3 consecutive times?

Error processing

100ms after EOT transmission

STX

ETX

46H 43H

SOH

F C

Transmission data

5

0

STX

0 2

ETX

Master station slave station

Master station slave station

Master station slave station

0