5 - 10

5. PARAMETERS

Class

No.

Symbol

Name and function

Initial

value

Unit

Setting

range

Control

mode

14

TQC

Torque command time constant

Used to set the constant of a low pass filter in response to the torque
command.

Torque command

TQC

TQC

Time

After
filtered

TQC: Torque command time constant

Torque

0

ms

0

to

20000

T

15

*SNO Station number setting

Used to specify the station number for serial communication.
Always set one station to one axis of servo amplifier. If one station
number is set to two or more stations, normal communication cannot
be made.

0

sta-

tion

0

to

31

P S T

B

asi

c p

ara

m

et

ers

16

*BPS Serial communication function selection, alarm history clear

Used to select the serial communication baudrate, select various
communication conditions, and clear the alarm history.

Serial baudrate selection
0: 9600 [bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]

Alarm history clear
0: Invalid
1: Valid
When alarm history clear is made valid,
the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting
is automatically made invalid (reset to 0).

Serial communication standard selection
0: RS-232C used
1: RS-422 used

Serial communication response delay time
0: Invalid
1: Valid, reply sent after delay time of 800 s or more

0000

Refer to
Name
and
function
column.

P S T