5 - 28

5. PARAMETERS

(3) Setting for use of A1SD75P

The A1SD75P also has the following electronic gear parameters. Normally, the servo amplifier side
electronic gear must also be set due to the restriction on the command pulse frequency (differential
400kpulse/s, open collector 200kpulse/s).

AP: Number of pulses per motor revolution
AL: Moving distance per motor revolution
AM: Unit scale factor

Command

value

Control

unit

AP

AM

AL

CMX

CDV

Deviation

counter

Electronic gear

Feedback pulse

Command

pulse

Servo amplifier

A1SD75P

Servo motor

Electronic gear

The resolution of the servo motor is 131072 pulses/rev. For example, the pulse command needed to

rotate the servo motor is as follows

Servo motor speed [r/min]

Required pulse command

2000

131072 2000/60 4369066 pulse/s

3000

131072 3000/60 6553600 pulse/s

For the A1SD75P, the maximum value of the pulse command that may be output is 200kpulse/s in the
open collector system or 400kpulse/s in the differential line driver system. Hence, either of the servo
motor speeds exceeds the maximum output pulse command of the A1SD75P.
Use the electronic gear of the servo amplifier to run the servo motor under the maximum output pulse
command of the A1SD75P.