Yaskawa MP2000 Series: User's Manual for Motion Programming User Manual
Page 308

10.2 Troubleshooting for Motion Programs
10-5
10
Troubleshooting
(2) Program Start Request Bit of Control Signal and Program Running Status Bit of Sta-
tus Flag
When the MP2000 system detects a status change in motion program control signal bit 0 (Program start request)
from OFF to ON, the motion program will start running. When the motion program successfully starts running,
status flag signal bit 0 (Program running) will turn ON. Status flag signal bit 0 (Program running) will turn OFF
when the END command in the motion program is executed.
To start the motion program again, turn motion program control signal bit 0 (Program start request) OFF, and
then turn it ON again.
Check the ON/OFF status of these signal by using the data trace function.
Status flag
Motion program
work register
Control signal
Interpolation override
System work number
1st word
If this bit turns ON, the motion
program will start running.
Program start request
Control signal, bit 0:
Status flag, bit 0:
Program running
Check to see if the program
start request bit is ON.
Bit 0
The motion program correctly started
if bit 0 is turned ON.
The motion program has correctly
started if the program running
bit is turned ON.
2nd word
3rd word
4th word
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D
Bit E
BitF
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D
Bit E
Bit F
Program running
Program paused
Stopped by program stop request
(Reserved by the system)
Program single-block operation stopped
(Reserved by the system)
(Reserved by the system)
(Reserved by the system)
Program alarm
Stopped by break point
(Reserved by the system)
In debug mode
Program type
Start request signal history
“No system work” error, Execution scan error
Main program No. over the range
Program operation start request
Program pause request
Program stop request
Program single-block mode selection
Program single-block operation start request
Program reset and alarm reset request
Program continuous operation start request
(Reserved by the system)
Skip 1 information
Skip 2 information
(Reserved by the system)
(Reserved by the system)
(Reserved by the system)
System work number setting
Interpolation override setting
(Reserved by the system)
Motion program end timing