8 Command Reference
8.9.14 ON-Delay Timer (TON): Counting unit: 0.01 second
8-154
8.9.14 ON-Delay Timer (TON): Counting unit: 0.01 second
(1) Overview
The TON command counts the milliseconds (in units of 10 ms) when the bit input is ON. When the counted
value is equal to the set value, the bit output will turn ON. If the bit input turns OFF during counting, the timer
operation will stop. After the bit input turns ON again, counting starts again from the beginning (0). In the regis-
ters for counting, the actual count (in units of 10 ms) is stored.
Note: The following versions of system software and programming tool MPE720 are required to use TON
commands.
(2) Format
• Milliseconds are not counted while the debugging operation is stopped.
Counting starts again from the current counted value after the debugging operation restarts.
• Be sure to designate bit input “DBxxxxxx&.”
Motion Programs
Sequence Programs
Not applicable
Applicable
MP2000 Series
Machine Controller
Required Version
MPE720
Required Version
All models
Ver.2.60 or later
MPE720 Ver.5
MPE720 Ver.5.38 or later
MPE720 Ver.6
MPE720 Ver.6.04 or later
MPE720 Ver.6.04Lite or later
DB000001 = DB000000 & TON (500 DW00001);
A B C D
Item
Description
Usable Registers
A
Bit output
• Bit type registers (Excluding # and C registers)
• The above registers with subscript
B
Bit input
• All bit type registers
• The above registers with subscript
C
Set value
• All integer type registers
• The above registers with subscript
• Constants (0 to 65535 (655.35 s): Every 10 ms)
D
Register for timer counting
• All integer type registers
• The above registers with subscript
IMPORTANT