The Safe Disable function can only be deactivated when a Run command is not active.
If Safe Disable was activated during stop, turn on both Safe Disable inputs by deactivating “Safe Torque Off” to resume normal

operation.
If Safe Disable was activated during run, remove the Run command then turn on the Safe Disable inputs before restarting the

drive.

n

Safe Disable Monitor Output Function and Digital Operator Display

Note:

Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-1,

ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.

Table C.13

explains the drive output and Safe Disable monitor state depending on the Safe Disable inputs.

Table C.13 Safety Input and EDM Terminal Status

Safe Disable Input Status

Safe Disable Status Monitor,

DM+ DM-

Drive Output Status

Digital Operator

Display

Input 1, H1-HC

Input 2, H2-HC

S6 Switch = “N.C.”

S6 Switch = “N.O.”

OFF

OFF

OFF

ON

Safely disabled,

“Safe Torque Off”

Hbb (flashes)

ON

OFF

ON

OFF

Safely disabled,

“Safe Torque Off”

HbbF (flashes)

OFF

ON

ON

OFF

Safely disabled,

“Safe Torque Off”

HbbF (flashes)

ON

ON

ON

OFF

Baseblock,

ready for operation

Normal display

Safe Disable Status Monitor

Note:

Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-1,

ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.

Slide Switch S6 controls the polarity of this signal. Refer to

Table C.13

for functionality.

With the Safe Disable monitor output (terminals DM+ and DM-), the drive provides a safety status feedback signal. This signal

should be read by the device that controls the Safe Disable inputs (PLC or a safety relay) in order to prohibit leaving the “Safe

Torque Off” status in case the safety circuit malfunctions. Refer to the instruction manual of the safety device for details on

this function.

Digital Operator Display

Note:

Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN 61800-5-1,

ISO/EN 13849 Cat. 3, IEC/EN 61508 SIL2, Insulation coordination: class 1.

When both Safe Disable inputs are open, “Hbb” will flash in the digital operator display.
If one Safe Disable channel is on while the other is off, “HbbF” will flash in the display to indicate that there is a problem in

the safety circuit or in the drive. This display should not appear under normal conditions if the Safe Disable circuit is utilized

properly.

Refer to Alarm Codes, Causes, and Possible Solutions on page 214

to resolve possible errors.

C.3 Safe Disable Input Function

370