C.2 ul and csa standards, Ul standards compliance, Crimping – Yaskawa CIMR-AU 200V Drives User Manual
Page 356

C.2 UL and CSA Standards
u
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and
evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL
certification, all components inside that product must also receive UL certification.
Figure C.7 UL/cUL Mark
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described
below must be met to maintain compliance when using this drive in combination with other equipment:
n
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
n
Ambient Temperature
IP20/NEMA Type 1 Enclosure: -10 to +40 °C
IP00 Open Type Enclosure: -10 to +50 °C
n
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed
closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0110 to
2A0415, 4A0058 to 4A0675, (4A1200 series dependant), and 5A0041 to 5A0242. Use only the tools recommended by the
terminal manufacturer for crimping. Refer to Closed-Loop Crimp Terminal section of the drive Technical Manual for closed-
loop crimp terminal recommendations.
Closed-Loop Crimp Terminal Recommendations
To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main
circuit terminals on models 2A0110 to 2A0415, 4A0058 to 4A0675, (4A1200 series dependant), and 5A0041 to 5A0242. Use
only the tools recommended by the terminal manufacturer for crimping. Yaskawa recommends UL listed crimp terminals
made by JST and Tokyo DIP (or equivalent) for the insulation cap.
matches the wire gauges and terminal screw
sizes with Yaskawa-recommended crimp terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque
Specifications table for the wire gauge and screw size for your drive model. Place orders with a Yaskawa representative or
the Yaskawa sales department.
Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.
Table C.6 Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model
Number
Tool
Insulation
Cap Model
No.
Code
<1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3
Machine No.
Die Jaw
200 V Class
2A0004
2A0006
2A0008
2A0010
14
M4
R2-4
YA-4
AD-900
TP-003
100-054-028
12
R5.5-4
TP-005
100-054-029
10
2A0012
14
14
M4
R2-4
YA-4
AD-900
TP-003
100-054-028
12
12
R5.5-4
TP-005
100-054-029
10
C.2 UL and CSA Standards
356
YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide