No.

(Addr

Hex.)

Name

LCD Display

Description

Values

Page

b3-29

(077C)

<4>

Speed Search Induced

Voltage Level

SpdSrch Ind Vlvl

Performs Speed Search when the motor induced voltage

exceeds the set level.

There is normally no need to change this parameter from the

default value, but if changes are necessary, try lowering this

value in small increments. When set too low, the drive will not

perform Speed Search.

Note:

This parameter is not available in models 4A0930

and 4A1200.

Default: 10%

Min.: 0

Max.: 10

b3-33

(0B3F)

<5>

Speed Search Selection

when Run Command is

Given during Uv

SpdSrch Start UV

0: Disabled

1: Enabled

Activates and deactivates Speed Search at start in accordance

with whether a Run command was issued during an

undervoltage (Uv) condition. Function is active when a

momentary power loss (L2-01 = 1 or 2), Speed Search at start

(b3-01 = 1), and coasting to a stop (b1-03 = 1) are enabled.

0: Disabled

1: Enabled

Note:

This parameter is not available in models 4A0930

and 4A1200.

Default: 0

Range: 0, 1

<1> Default setting is determined by parameter A1-02, Control Method Selection.
<2> Default setting is determined by parameter o2-04, Drive Model Selection.
<3> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<4> Available in drive software versions PRG: 1018 and later.
<5> Available in drive software versions PRG: 1019 and later.

u

b4: Timer Function

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b4-01

(01A3)

Timer Function On-

Delay Time

Delay-ON Timer

Sets the on-delay and off-delay times for a digital timer output

(H2-oo = 12).

The output is triggered by a digital input programmed to

H1-oo = 18).

Default: 0.0 s

Min.: 0.0

Max.: 3000.0

b4-02

(01A4)

Timer Function Off-

Delay Time

Delay-OFF Timer

Default: 0.0 s

Min.: 0.0

Max.: 3000.0

b4-03

(0B30)

<1>

H2-01 ON Delay Time

H2-01 ON Delay

Sets the length of the delay time for contact outputs to open or

close for the related functions set in H2-oo.

Note:

This parameter is not available in models 4A0930

and 4A1200.

Default: 0 ms

Min.: 0

Max.: 65535

b4-04

(0B31)

<1>

H2-01 OFF Delay Time H2-01 OFF Delay

b4-05

(0B32)

<1>

H2-02 ON Delay Time

H2-02 ON Delay

b4-06

(0B33)

<1>

H2-02 OFF Delay Time H2-02 OFF Delay

b4-07

(0B34)

<1>

H2-03 ON Delay Time

H2-03 ON Delay

b4-08

(0B35)

<1>

H2-03 OFF Delay Time H2-03 OFF Delay

<1> Available in drive software versions PRG: 1019 and later.

B.2 b: Application

270

YASKAWA ELECTRIC TOEP C710616 41E YASKAWA AC Drive - A1000 Quick Start Guide