Yaskawa CIMR-AU 200V Drives User Manual
Page 216

<1>
oH5
Motor Overheat (NTC Input)
The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2)
<1> Detected in models 4A0930 and 4A1200.
oL3
Overtorque 1
Drive output current (or torque in OLV, CLV, AOLV/PM, and CLV/PM) was greater than L6-02 for longer
than the time set to L6-03.
oL4
Overtorque 2
Drive output current (or torque in OLV, CLV, AOLV/PM, CLV/PM) was greater than L6-05 for longer than
the time set to L6-06.
oL5
Mechanical Weakening Detection 1
Overtorque occurred, matching the conditions specified in L6-08.
oS
Overspeed
The motor speed feedback exceeded the F1-08 setting.
ov
DC Bus Overvoltage
The DC bus voltage exceeded the trip point.
• For 200 V class drives: approximately 410 V
• For 400 V class drives: approximately 820 V (740 V when E1-01 is less than 400)
• For 600 V class drives: approximately 1040 V
PASS
MEMOBUS/Modbus Comm. Test Mode Complete
PGo
PG Disconnect (for Control Mode with PG)
Detected when no PG pulses are received for a time longer than setting in F1-14.
PGoH
PG Hardware Fault (detected when using a PG-X3 option card)
PG cable has become disconnected.
rUn
Motor Switch during Run
A command to switch motors was entered during run.
SE
MEMOBUS/Modbus Communication Test Mode Error
Note:
This alarm will not trigger a multi-function output terminal that is set for alarm output
(H2-oo = 10).
<1>
THo
Thermistor Disconnect
The thermistor used to detect motor temperature has become disconnected.
<1> Detected in models 4A0930 and 4A1200.
TrPC
IGBT Maintenance Time (90%)
IGBTs have reached 90% of their expected performance life.
UL3
Undertorque Detection 1
Drive output current (or torque in OLV, CLV, AOLV/PM, and CLV/PM) less than L6-02 for longer than
L6-03 time.
UL4
Undertorque Detection 2
Drive output current (or torque in OLV, CLV, AOLV/PM, and CLV/PM) less than L6-05 for longer than
L6-06 time.
Uv
Undervoltage
One of the following conditions was true when the drive was stopped and a Run command was entered:
• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was opened.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is not 0 and DC bus voltage
is under L2-05.
5.3 Alarm Detection
216